Monocrystalline Silicon Differential Pressure TransmitterModel:SYDM26

Update Terakhir
:
12 / 07 / 2024
Min. Pembelian
:
1 Unit
Dilihat Sebanyak
:
16 kali

Harga

CALL
Bagikan
:
*Instrumentation, Control System, Automation, Cooler & Heat Exchanger, Electrical, Mechanical, Analyzers, Fabricator & Engineering Service & Training*

Detail Monocrystalline Silicon Differential Pressure TransmitterModel:SYDM26

Monocrystalline Silicon Differential Pressure Transmitter ( Model: SYDM-26 )

Monocrystalline silicon differential pressure transmitter is used to measure the differential pressure of liquid, steam or gas.
If some industry has high requirement, core components can adopt Endress+Hauser’s ceramic sensor and Manufacture technology.

Technical data:
● Principle: Monocrystalline silicon ( with Lightning protection design )
● Applicable medium: Liquid, Gas, Steam
● DP Range:

Range
code
Minimum
Span
( Kpa )
Sensor’s range limit ( Kpa )
Static pressure rating
Option
Low range limit
(LRL)
Upper range limit
(URL)
A
1
-6
6
4 Mpa
B
2
-40
40
4 Mpa, 16 Mpa
C
12.5
-100
250
4 Mpa, 16 Mpa
D
50
-100
1000
4 Mpa, 16 Mpa
E
150
-100
3000
4 Mpa, 16 Mpa
F
500
-100
10000
16 Mpa
● Turndown ratio: 100 : 1
● Accuracy option: ±0.075%, ±0.1%, 0.2%
● Span effect:
> For accuracy 0.075% (Range code B – F):
when Turndown ratio is 1:1 ~ 10:1, effect is 0.075% of calibration range;
when Turndown ratio is larger than 10:1, effect is ±[ 0.002×Turndown ratio -0.1 ] %.
> For accuracy 0.1% (Range code A – F):
when Turndown ratio is 1:1 ~ 10:1, effect is 0.1% of calibration range;
when Turndown ratio is larger than 10:1, effect is ±[0.025×Turndown ratio -0.125 ] %.
> For accuracy 0.2% (Range code A – F):
when Turndown ratio is 1:1 ~ 10:1, effect is 0.2% of calibration range;
when Turndown ratio is larger than 10:1, effect is ±[0.03×Turndown ratio -0.1 ] %.
● Stability: within 36 months, error is ±0.2% of Maximum span
● Temperature effect:
> For accuracy 0.075%: error of zero point or full Span is ±0.15% of Maximum span / 28℃
> For accuracy 0.1%: error of zero point or full Span is ±0.2% of Maximum span / 28℃
> For accuracy 0.2%: error of zero point or full Span is ±0.25% of Maximum span / 28℃
● Power supply effect: less than ±0.005% of calibration range / V
● Vibration effect: less than ±0.05% of Maximum span / g
● Installation effect: zero point drift is not more than 0.25Kpa, this error can be eliminated by zero point calibration, which does not affect instrument range.
● Electrical characteristics
> Power supply (E ): 24VDC ( 10.5 ~ 36 VDC )
> Output option: 4-20mA , 4-20mA(2-wire) + HART protocol

● Load (R) characteristic:



Parameter of intrinsically safe explosion-proof: Ui=28VDC, Ii=93mA, Pi=0.65W, Ci=0μF, Li=0mH
Electromagnetic compatibility: comply with IEC 61000-4