Field Instrumentation & Controls

Capacitance Differential Pressure Transmitter ( Model: SYDM-24 )

Update Terakhir
:
12 / 07 / 2024
Min. Pembelian
:
1 Unit
Dilihat Sebanyak
:
11 kali

Harga

CALL
Bagikan
:
*Instrumentation, Control System, Automation, Cooler & Heat Exchanger, Electrical, Mechanical, Analyzers, Fabricator & Engineering Service & Training*

Detail Capacitance Differential Pressure Transmitter ( Model: SYDM-24 )

Capacitance Differential Pressure Transmitter ( Model: SYDM-24 )

SYDM24 is capacitance type differential pressure transmitter, easy to install and use, safe and explosion-proof.
Adopt advanced integrated circuit and SMT technology,
If some industry has high requirement, core components can adopt Endress+Hauser’s ceramic sensor and Manufacture technology.
High precision, small size, easy to adjust, good stability, strong ability of one-way overload protection;
It is widely used in industry of power, metallurgy, petrochemical, pharmaceutical, instrument processing etc.
CE certificate, SIL certificate, CNEX certificate.

Technical Data:

● Applicable medium: liquid, gas, steam
● DP Range option:

Range code
Range
Static pressure rating option
A
– 0.1 ~ 1 Kpa
4 Mpa
B
0 -1 ~ 6 Kpa
4 Mpa
C
0 – 6 ~ 40 Kpa
4 Mpa, 10 Mpa, 16 Mpa
D
0 – 40 ~ 250 Kpa
4 Mpa, 10 Mpa, 16 Mpa
E
0 – 0.16 ~ 1 Mpa
4 Mpa, 10 Mpa, 16 Mpa
F
0 – 0.4 ~ 2.5 Mpa
4 Mpa, 10 Mpa, 16 Mpa
G
0 – 1.6 ~ 10 Mpa
16 Mpa
Hot Tags: water flow meter,thermal mass flow meter,Level Transmitter,ultrasonic level transmitter

● Output signal: 4-20mA (Option: HART [belong to HART Communication Foundation], Square root output), Power supply: 12 ~ 45VDC, Generally 24VDC. Load: RL= (Vs – 12V) / 0.023A ( RL is Maximum load, ≤ 600 Ω, Vs is power supply voltage)

● Range and zero point can be adjusted through the built-in adjusting screw nut or through HART communicator.
● Positive and negative migration:
The maximum positive migration is the difference between the URL (Instrument’s upper range limit) and the setting range, the maximum negative migration is URL.
● Fault alarm: The fault is detected by the self-diagnosis program. It will alarm when the analog output is higher than 22mA or lower than 3.9mA.
● Operation temperature:
-40 ~ 85℃ (analog transmitter), -10 ~ 80℃ (smart transmitter)
-40 ~ 104℃ (sensor: Silicone oil filling), -184 ~ 71℃ (sensor: Inert oil filling)
Flange type remote seal (fill ordinary silicone oil): -40 ~ 150 ℃
Flange type remote seal (fill high temp. silicone oil): 15 ~ 315 ℃
● Storage temperature: 40 ~ 50℃
● Startup time: < 2s
● Volumetric absorption: < 0.16 cm3
● Damping: Adjustable in range 0 ~ 16 s
● Accuracy: 0.2%FS (standard configuration) , 0.1%FS (option)
● Stability: free of maintain within one year
● Temperature effect:
Total error varies <±0.3 URL every 10℃ for the range code C, D, E, F, G
The total error is doubled every 10℃ for the range code A, B
● Static pressure effect:
DP transmitter: For static pressure 14 Mpa, ±0.25% URL or ±0.5% range code 3.
For static pressure 32 Mpa, ±0.2% URL. Under process pressure, adjust zero point for correction.
● Vibration effect: 0.1% URL, 10~55 Hz, S=0.15mm, at any direction.
● Power supply effect: < 0.005% of the output range / V